The High Volume Industrial Exhaust Fan is a heavy-duty, wall-mounted axial fan designed for high-volume, low-pressure industrial ventilation. It is used for heat removal, air exchange, moisture control, and continuous exhaust in large commercial, industrial, agricultural, and high-bay buildings.
Airflow & Product Specifications
|
Model |
Blade Diameter |
Speed |
Motor Power |
Airflow @ 0" SP |
Airflow @ 0.10" SP |
Airflow @ 0.125" SP |
Dimensions (W×H×D) |
Weight |
|
HEF-1060 |
1000 mm / 39" |
450 RPM |
0.75 / 1.0 kW/HP |
28,000 CFM |
23,800 CFM |
22,200 CFM |
1080×1080×400 mm |
48 kg |
|
HEF-1250 |
1250 mm / 50" |
420 RPM |
1.1 / 1.5 kW/HP |
38,000 CFM |
32,300 CFM |
30,100 CFM |
1300×1300×450 mm |
65 kg |
|
HEF-1380 |
1380 mm / 54" |
370 RPM |
1.5 / 2.0 kW/HP |
44,500 CFM |
37,800 CFM |
35,200 CFM |
1380×1380×450 mm |
78 kg |
|
HEF-1460 |
1460 mm / 57" |
340 RPM |
2.2 / 3.0 kW/HP |
51,000 CFM |
43,300 CFM |
40,400 CFM |
1500×1500×450 mm |
86 kg |
Motor & Electrical Configuration
|
Parameter |
Standard |
Optional |
|
Voltage |
380–415V |
220–240V / 460–480V |
|
Phase / Frequency |
3-Phase / 50Hz |
1-Phase (HEF-1060 only) / 60Hz |
|
Insulation |
Class F |
Class H |
|
Protection |
IP55 |
IP65 |
|
Duty |
S1 Continuous |
- |
|
Starting |
DOL |
Soft Starter / VFD |
Exhaust Applications
Manufacturing Workshops: Used for general heat removal and exhaust of welding fumes, oil mist, and other airborne contaminants in suitable workshop environments.
Warehouses & Logistics Hubs: Used to increase air exchange and reduce heat accumulation in high-bay facilities.
Compressor & Power Rooms: Discharges continuous heat output from air compressors, transformers, and standby power generators.
Agricultural Facilities: Regulates temperature buildup and moisture levels in commercial livestock barns, poultry houses, and greenhouses.
Fan Construction
Housing Assembly: Heavy-duty hot-dip galvanized steel housing with a specified zinc coating weight of 275 g/m². Stainless steel 304 housing is available for HEF-1380 and HEF-1460 configurations.
Impeller Blades: Stamped SS304 or molded FRP (Fiber-Reinforced Plastic) blades, dynamically balanced.
Installation
Wall Opening Preparation: Fits structural steel framing, precast concrete panels, or masonry cutouts through corner-flange anchors.
Mounting & Alignment: Position the unit within the prepared wall opening and secure the corner-flange anchors to maintain a stable, level installation and consistent clearance around the housing.
Electrical Connection & Commissioning: Connect the specified power supply and control wiring according to the wiring diagram, then verify secure terminals, correct polarity/voltage, and proper operation before final enclosure or panel installation.
Maintenance & Replacement Parts
Belt Inspection: Periodic checking of belt tension and pulley alignment is recommended for belt-driven models.
Impeller Cleaning: Regular removal of dust buildup on blades preserves dynamic balance and avoids motor overload.
Spare Parts Availability: Direct factory availability for replacement blade hubs, drive belts, IP55 motors, IP55 junction boxes, and shutter louvers.
Certifications & Compliance
EAEU Declaration of Conformity: Certified under TR CU 010/2011 (Machinery Safety) and TR CU 020/2011 (EMC Compliance).
ISO Quality Standards: ISO 9001:2015 (Quality), ISO 14001:2015 (Environmental), and ISO 45001:2018 (Occupational Health & Safety) certified production facilities.



FAQ
Q: What is the minimum order quantity (MOQ)?
A: The standard MOQ is 2 units per model for stock configurations or 1 unit for custom-voltage/blade-material orders. Orders below 2 units incur a 15% small-order surcharge.
Q: What is the production lead time after order confirmation?
A: Standard models (HEF-1060/1250) ship within 15–20 working days. Custom-voltage or stainless-steel-housing models (HEF-1380/1460) require 25–35 working days for housing fabrication.
Q: What warranty period is offered, and what does it cover?
A: An 18-month warranty from the bill-of-lading date covers motor windings, bearings, and impeller-balance defects. It excludes damage from incorrect voltage connections or improper make-up-air installation.
Q: How loud is the fan during operation?
A: Sound pressure ranges from 68 dB(A) for the HEF-1060 to 76 dB(A) for the HEF-1460, measured at 1 meter.
Q: What payment terms are accepted for international orders?
A: We accept a 30% T/T deposit, with the balance paid against a copy of the bill of lading, or an irrevocable L/C at sight for orders above USD 20,000.
Q: Can the fan be customized?
A: Yes. Voltage, blade material (SS304 or FRP), housing color (RAL code), and OEM nameplate/labeling can be customized, typically adding 5–7 days to the standard lead time.
Q: How many units fit in a standard shipping container, and how are they packaged?
A: A 40HQ container holds approximately 40 HEF-1060 units or 24 HEF-1460 units. Each fan is packed in a plywood crate with corner-flange protection to prevent shutter damage during transit.
Q: What after-sales support is available overseas?
A: Spare parts-including motors, blade hubs, and shutter louvers-are available for international dispatch within 5 days. Technical support via video call is provided for on-site troubleshooting within 24 hours of request.
Hot Tags: high volume industrial exhaust fan, China high volume industrial exhaust fan manufacturers, suppliers, factory, High Pressure Industrial Exhaust Fan, High Temperature Industrial Exhaust Fan, High Volume Industrial Exhaust Fan, Industrial Centrifugal Exhaust Fan, industrial exhaust fans